安裝使用多極管式滑觸線的注意事項:
Installation using multipole tube slide wire notice:
1、潮濕狀態或室外使用,請用絕緣子的懸吊螺栓。
1, moist state or outdoor use, please use the suspension insulator bolt.
2、全線安裝后,測量外殼與帶電體間絕緣電阻不得小于5MW,測量外殼的電連續性,將一端導軌與外殼搭接,然后另一端測量回路是否暢通,測定完畢后,拆除連接部分。多級管式滑觸線
2, all after installation, measure the insulation resistance between the shell and the charged body shall not be less than 5 mw, measuring casing electrical continuity, guide rail and the shell will end lap, and then the other end of the measurement circuit is open, after the determination, remove the connection parts.
3、為防止集電器頸部磨損,對集電器頸部外包不銹鋼護殼、或保護滾柱應定期檢查,及時更換。
3, in order to prevent the collector neck wear and tear, the collector neck outsourcing stainless steel shell, or protect roller should be checked regularly, timely replacement.
4、室外雨雪、濕度較大場所,導管外殼連接處,絕緣粘帶纏覆后再蓋連接夾,以防止雨水侵入。
4, outdoor snow and rain, humidity larger place, catheter shell joints, insulation adhesive tape wrapped cover again after connecting clip, in order to prevent water invasion.
5、鋁合金型外殼必須良好的接地,全線外殼保證電連續性,外殼每隔25m-30m接地一次。
5, aluminum alloy shell must be good grounding, across the shell to ensure electrical continuity, shell every 25 m to 30 m ground again.