Dial-A-Function儀表歧管和閥門經過精心設計,可通過保護...流量和壓力控制系統的準確性...避免人員受到不安全狀況的影響以及系統內的硬件來減少停機時間和維修成本

PRGM7-TV-SS-AF1F2系列

PRGM7-TV-SS-AF1F2系列

詢價:306-167-18-20

DIAL-A-FUNCTION®
Design Features
Various U.S. and Foreign patents and patents pending.
®Registered trade name
 


How it Works
Why Dial-A-Function
Additional Dial-A-Function Benefits
Dial-A-Function Manifolds vs. Manually Sequenced Manifolds
Theory of Operation 

An Improved Design Lowers Costs:
Dial-A-Function instrument manifolds and valves are engineered to reduce downtime and service costs by guarding ... the accuracy of the flow and pressure control systems ... the personnel from unsafe conditions ... and the hardware within the system.

How it Works:Top

Dial-A-Function is a unique multi-function soft seat rotary valve design that allows the operator to simply dial the service mode, thus assisting him in the responsibility of opening and closing a number of valves in exactly the right sequence.

Why Dial-A-Function?:Top

A manually sequenced 3 valve manifold has 8 possible valve positions. A 5 valve manifold has 32 possible positions, each with even more sequences to arrive at the proper service mode. With this large number of variables, there is an unnecessarily high probability of human error. 

Problems caused by improper valve position or sequence:

Error A SchematicERROR A
The equalizer is left open or is opened before the block valve is fully closed (caused by operating the manifold with two hands).
PROBLEM:
  1. The seal liquid (antifreeze or water [steam applications]) in the piping would unknowingly be flushed out, resulting in transmitter damage and dangerous loss of process control.
  2. The liquid seal level would become unbalanced resulting in a deceiving and false transmitter output.

DIAL-A-FUNCTION SOLUTION:
This error is theoretically impossible with Dial-A- Function. The high pressure signal is automatically blocked before the equalizer is opened.
Error B SchematicERROR B
The equalizer is not fully closed or is leaking.
PROBLEM:
A very deceiving and false transmitter output resulting in inaccurate measurement or control.
DIAL-A-FUNCTION SOLUTION:
  1. An equalizer leak test mode is available to give absolute test for equalizer leakage
  2. Reduces possible errors by clearly marking the valve mode on the manifold body and the operating mode can be determined visually even from a distance
Error C SchematicERROR C
While pressurizing, a block valve could be opened before the equalizer is opened.
PROBLEM:
Full process pressure would hit one side of the transmitter causing shifts in zero and span or permanent damage.
DIAL-A-FUNCTION SOLUTION:
  1. Includes a convenient repressurize mode
  2. Offers an Interlocking Protection (IP) option to protect the transmitter during pressurizing (see below)
IP Error C Solution
Interlocking Protection Solution to Error C:
During startup, without the IP option, if the operator fails to rotate the BLOCK handle to NORMAL before the ZERO handle is rotated to NORMAL, error C will occur.
The IP option mechanically interlocks the valves, causing the BLOCK VALVE to simultaneously rotate to NORMAL while the ZEROING VALVE is being rotated. The IP option guards against static pressure hitting one side of the transmitter causing loss of calibration or damage.
Error D SchematicERROR D
A block valve could be left closed when returning to service.
PROBLEM:
The transmitter will now be measuring pressure instead of flow. This will result in major measurement and control problems. 
DIAL-A-FUNCTION SOLUTION:
  1. Includes a visual indication of the correct valve position. This greatly reduces the chance the error will go undetected.
  2. Offers an Interlocking Protection (IP) option that protects the transmitter from this possible error (see below)
IP Error D Solution
Interlocking Protection Solution to Error D:
If the ZERO handle is left in the BLOCK mode, the output of the transmitter would be zero (4mA) and the operator would be alerted to the problem.
If only the ZERO handle is returned to NORMAL, the mechanical linkage automatically returns the BLOCK handle to the NORMAL mode. This reduces the possibility of the manifold trapping pressure resulting in a transmitter output of pressure rather than flow.
Error E SchematicERROR E
The equalizer could be left closed while a vent valve on one side of the transmitter was opened to depressurize the system.
PROBLEM:
Full process pressure would remain on one side of the transmitter causing shifts in zero and span or permanent damage.
DIAL-A-FUNCTION SOLUTION:
  1. The MM6UC has a built-in depressurize mode that automatically vents both sides of the transmitter through one vent valve.
  2. The (IP) option, plus replacing the transmitter vent valves with plugs, reduces this possible error (see below).
IP Error E Solution
Interlocking Protection Solution to Error E:
During depressurizing, without the IP option, if the operator fails to select the ZERO mode before the DEPRESSURIZE mode, error E will occur.
The IP option mechanically links the valves so, as the BLOCK handle is rotated to the DEPRESSURIZE mode, the ZERO handle is automatically rotated to the ZERO mode. The transmitter is protected from damage caused by full process pressure remaining on one side during depressurizing.


Additional Dial-A-Function Benefits:Top
  • The operator can visually inspect the manifold from a distance to determine the operating mode by looking at the position of the large arrowhead handles.
  • Dial-A-Function reduces the time required to service a system.
  • An Interlocking Protection (IP) Option is available to give maximum operator assistance to overcome errors which can cause transmitter damage, inaccuracy and unsafe conditions.

Dial-A-Function vs. Manually Sequenced Valves:Top
Type of ManifoldManually Sequenced ManifoldsDIAL-A-FUNCTION
3 Valve
3-valve Schematic
5 Valve
5-valve Schematic

Dial-A-Function Schematic


Interlocking Protection (IP) Option
Mechanically interlocks the valves to protect the transmitter from damage and inaccuracy caused by an error in valve position or sequence.
Number of valve positions8
( 2 3 )
32
( 2 5 )
Dial-a-Function has only the required number of positions (2 to 7), specified by model.
Selection of position and sequencePosition and sequence are selected by the operator.Automatic positioning and sequencing of the selected function.
Probable errors due to improper position or sequence1. Transmitter damage
2. Inaccurate measurement or control
3. Unsafe conditions
1. None (after system is pressurized)
2. IP Option guards the system even during startup

 

Theory of Operation:       Model MM6UCTop
1) NORMAL

Normal


2) ZERO

Zero


3) DEPRESSURIZE

Depressurize


4) ISOLATION

Isolation


5) AND/OR CALIBRATION

Calibration


6) REPRESSURIZE

Repressurize


7) RETURN TO NORMAL

Normal Return

Note the logical sequence of handle positions as you select the modes necessary to advance from NORMAL through CALIBRATEand then return to NORMAL (Steps 1 to 7). This is the same order of modes you would need on a manually sequenced manifold. However, to accomplish this with a manually sequenced manifold, you would need to know which of the 3 valves to open or close and in what sequence.

With a DIAL-A-FUNCTION manifold you just dial the next position ... forward or reverse and you will automatically be in the correct mode.

Certain models can also be used to test for equalizer leakage as shown below:


TEST EQUALIZER LEAKAGE
Equalizer Leakage 

How to Test Equalizer Leakage With IP Option:
  1. Pull on handle lock button and rotate handle clockwise approximately 60º
  2. Test for leakage by venting the equalizer and checking for continuous flow
  3. To stop leakage SLIGHTLY tighten the packing nut under the ZERO HANDLE. If leakage does not stop, tighten the BLOCK HANDLE packing nut before additional tightening of the ZERO HANDLE packing nut
  4. Return the handle to normal and retighten the cap screw